DocumentCode
3400279
Title
Analysis of Operation of Synchronous Generator under the Distortion of Harmonic Current
Author
Wang Jin-quan ; Song Peng-chao ; Cui Chen-hua ; Li Jian-ke ; Yang Tao
Author_Institution
Eng. Inst. of Eng. Corps, PLA Univ. of Sci. & Technol., Nanjing, China
fYear
2012
fDate
27-29 March 2012
Firstpage
1
Lastpage
4
Abstract
When diesel generator supplies power to nonlinear load, harmonic current will flow through its armature. This part of current will distort the armature reaction. This article analysed how harmonic current influence the magnetic field inside the synchronous generator, derived a formula that can describe the electromagnetic torque pulsation brought by harmonic current, and anaysed the electromotive force distortion, then gave an example based on MATLAB model. The example demonstrates how diesel generator vibrates under the distortion of harmonic current.
Keywords
diesel-electric generators; harmonic distortion; synchronous generators; Matlab model; armature reaction; diesel generator; electromagnetic torque pulsation; electromotive force distortion; harmonic current distortion; magnetic field; nonlinear load; synchronous generator operation; Electromagnetics; Harmonic analysis; Power harmonic filters; Synchronous generators; Torque;