Vacuum switch-disconnectors : 2. Compliance with insulation coordination
Author
Schellekens, H. ; Gal, I. ; Goulielmakis, D.
Author_Institution
Medium Voltage Dev., Schneider Electr., Varces
Volume
1
fYear
2008
fDate
15-19 Sept. 2008
Firstpage
153
Lastpage
156
Abstract
The behaviour under lightning is simulated numerically for vacuum switch-disconnectors (standard deviation StD of 16%) and gas switch-disconnectors (StD of 5%) in a critical case of a MV/LV distribution station connected to a single overhead line. Lightning activity is simulated in accordance with the guidelines of Insulation Coordination, IEC60071-2. The influence of protective measures by surge arresters is taken into account. If correct protection measures are taken, the time to failure exceeds 1000 years for both technologies. Without such protection the time to failure reduces to 100 years. The differences due to the technologies are minor (~30%) with an advantage for vacuum in the latter case and for gas in the former case. It is conclude that vacuum permits to realise reliable disconnector function in accordance with the performance criterion of insulation coordination and with the same level of reliability as SF6.
Keywords
power overhead lines; vacuum interrupters; vacuum switches; IEC60071-2; MV-LV distribution station; SF6 reliability; gas switch-disconnectors; lightning activity; single overhead line; vacuum interrupters; vacuum switch-disconnectors; Breakdown voltage; Dielectrics and electrical insulation; Electric breakdown; IEC standards; Lightning; Medium voltage; Protection; Surges; Switches; Vacuum breakdown;
fLanguage
English
Publisher
ieee
Conference_Titel
Discharges and Electrical Insulation in Vacuum, 2008. ISDEIV 2008. 23rd International Symposium on
Conference_Location
Bucharest
ISSN
1093-2941
Print_ISBN
978-973-755-382-9
Electronic_ISBN
1093-2941
Type
conf
DOI
10.1109/DEIV.2008.4676742
Filename
4676742
Link To Document