DocumentCode :
3406091
Title :
The effect of corona wire heating on the ozone generations in an air cleaning electrostatic precipitator
Author :
Ohkubo, T. ; Hamasaki, S. ; Nomoto, Y. ; Chang, J.S. ; Adachi, T.
Author_Institution :
Dept. of Electr. Eng., Oita Univ., Japan
fYear :
1988
fDate :
2-7 Oct. 1988
Firstpage :
1647
Abstract :
The effect of corona wire surface temperature on ozone generation in an air-cleaning electrostatic precipitator is studied experimentally. The results show that significant ozone concentrations are only observed in a narrow region near downstream of the corona wire for positive coronas. From surface temperature measurements using infrared imaging, it is observed that the heat generated by corona discharge alone only increases the surface temperature of corona wire by few centigrades. Ozone generated by corona discharges can be significantly decreased by external heating of the wire.<>
Keywords :
air conditioning; corona; electrostatic precipitators; ozone; air conditioning; corona wire heating; electrostatic precipitator; infrared imaging; ozone generation; positive coronas; Corona; Electrostatic precipitators; Infrared heating; Infrared imaging; Surface discharges; Temperature measurement; Wire;