DocumentCode :
3406303
Title :
Plasma parameters after a forced extinguishing of the diffuse vacuum arc
Author :
Klajn, Antoni
Author_Institution :
Inst. of Electr. Power Eng., Wroclaw Univ. of Technol., Wroclaw
Volume :
2
fYear :
2008
fDate :
15-19 Sept. 2008
Firstpage :
365
Lastpage :
368
Abstract :
A series of experiments were performed in order to optimise the forced vacuum arc current commutation with the counter-pulse current method. The experiments were performed in a laboratory arrangement with parameters representatives for the low-voltage vacuum switches. The tested vacuum arc current with values 400 A and 600 A was interrupted with a counter-pulse current at falling rates from 2 A/mus up to 90 A/mus. The main measured parameters were: ion energy and residual charge after the current zero as function of the forced falling rate of the arc current. The results can be useful in modelling and design.
Keywords :
vacuum arcs; vacuum switches; counter-pulse current method; diffuse vacuum arc; ion energy; low-voltage vacuum switches; plasma parameters; residual charge; Charge measurement; Current measurement; Energy measurement; Force measurement; Laboratories; Optimization methods; Plasmas; Switches; Testing; Vacuum arcs;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Discharges and Electrical Insulation in Vacuum, 2008. ISDEIV 2008. 23rd International Symposium on
Conference_Location :
Bucharest
ISSN :
1093-2941
Print_ISBN :
978-973-755-382-9
Electronic_ISBN :
1093-2941
Type :
conf
DOI :
10.1109/DEIV.2008.4676804
Filename :
4676804
Link To Document :
بازگشت