Title :
Voltage inversion due to UPFC presence on second circuit of double circuit transmission line causing distance relay mal-operation
Author :
Kazemi, A. ; Jamali, S. ; Shateri, H.
Author_Institution :
Center of Excellence for Power Syst. Autom. & Oper., Iran Univ. of Sci. & Technol., Tehran
fDate :
June 30 2008-July 2 2008
Abstract :
This paper discusses distance relay maloperation in the presence of unified power flow controller (UPFC) on the second circuit of a double circuit transmission line. This is done by presenting the measured impedance at the relaying point in the case of UPFC presence at the near end of the second circuit. The measured impedance at the relaying point is greatly influenced in the presence of UPFC on the transmission line or even in the case of installing UPFC on the near end of the second circuit. The measured impedance at the relaying point depends on many factors including power system structural conditions, the pre-fault loading, the ground fault resistance, and UPFC structural and controlling parameters.
Keywords :
earthing; load flow; power control; power transmission faults; power transmission protection; relay protection; transmission line theory; UPFC presence; control parameters; distance relay maloperation; double circuit transmission line; ground fault resistance; impedance; power system structural conditions; pre-fault loading; unified power flow controller; voltage inversion; Distributed parameter circuits; Electrical resistance measurement; Impedance measurement; Load flow; Power system relaying; Power transmission lines; Protective relaying; Relays; Transmission line measurements; Voltage;
Conference_Titel :
Industrial Electronics, 2008. ISIE 2008. IEEE International Symposium on
Conference_Location :
Cambridge
Print_ISBN :
978-1-4244-1665-3
Electronic_ISBN :
978-1-4244-1666-0
DOI :
10.1109/ISIE.2008.4676929