Title :
Results of full-scale fire tests with electrical nonmetallic conduit and insulated wire in a vertical riser duct
Author :
McClung, L. Bruce ; Mueller, John F. ; Goldman, Mark E. ; Myers, Brenda C.
Author_Institution :
Union Carbide Corp., South Charleston, WV, USA
fYear :
1988
fDate :
2-7 Oct. 1988
Firstpage :
1921
Abstract :
Full-scale fire tests were conducted during the summer of 1987 at the New York State Academy of Fire Science in Montour Falls, New York to determine if the results of small-scale smoke and toxicity tests reflected real-world conditions represented by full-scale testing. These tests were performed with 20ft-long sample bundles of conduit and wire hanging vertically in a 10 in-square riser duct installed in the Academy´s three-story, reburnable, arson simulation and fire-training building. Present commercially available materials and novel reduced-emission materials were tested, and the results compared. The full-scale test results correlated with those from small-scale tests, with the reduced-emissions material producing substantially less smoke and being nonlethal under the test conditions.<>
Keywords :
cable insulation; electric conduits; fires; testing; wires (electric); USA; fire tests; insulated wire; nonmetallic conduit; reduced-emission materials; riser duct; safety; smoke; toxicity tests; Ducts; Fires; Materials testing; Performance evaluation; Wire;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industry Applications Society Annual Meeting, 1988., Conference Record of the 1988 IEEE
Conference_Location :
Pittsburgh, PA, USA
Type :
conf
DOI :
10.1109/IAS.1988.25319
Filename :
25319
Link To Document :
بازگشت