DocumentCode
3412382
Title
Control of Doubly Fed Induction Generator under symmetrical voltage dips
Author
López, Jesús ; Sanchis, Pablo ; Gubía, Eugenio ; Ursúa, Alfredo ; Marroyo, Luis ; Roboam, Xavier
Author_Institution
Dept. of Electr. & Electron. Eng., Public Univ. of Navarre, Pamplona
fYear
2008
fDate
June 30 2008-July 2 2008
Firstpage
2456
Lastpage
2462
Abstract
Doubly Fed Induction Generator (DFIG) is largely used in wind generators. It provides variable speed characteristics in a cost-effective way. The main drawback of this machine is its sensitivity to grid disturbances. Voltage dips cause overvoltages to appear in the rotor that can surpass the converter limits. Additionally, variations of the grid voltage cause the stator flux to oscillate at the grid frequency. This paper proposes a novel control strategy to overcome these problems; furthermore, it reduces the rotor voltage, improving the control of the rotor current and it accelerates the dumping of the flux oscillations.
Keywords
asynchronous generators; electric current control; machine control; overvoltage; power supply quality; rotors; stators; wind power plants; doubly fed induction generator; flux oscillations; grid disturbances; grid frequency; rotor voltage; stator flux; symmetrical voltage dips; Induction generators; Protection; Reactive power; Rotors; Stators; Surges; Voltage control; Voltage fluctuations; Wind energy generation; Wind turbines;
fLanguage
English
Publisher
ieee
Conference_Titel
Industrial Electronics, 2008. ISIE 2008. IEEE International Symposium on
Conference_Location
Cambridge
Print_ISBN
978-1-4244-1665-3
Electronic_ISBN
978-1-4244-1666-0
Type
conf
DOI
10.1109/ISIE.2008.4677148
Filename
4677148
Link To Document