DocumentCode
3417962
Title
Some study on identification of ill-conditioned processes for control
Author
Stec, Przemyskaw ; Zhu, Yucai
Author_Institution
Dept. of Autom. Control, Silesian Tech. Univ., Gliwice, Poland
Volume
2
fYear
2001
fDate
2001
Firstpage
1202
Abstract
The identification of ill-conditioned processes is considered. For this class of processes, good estimates of individual transfer functions do not guarantee good closed-loop behaviour; it is essential to have good estimation of the very small differences between certain transfer functions, or, the so called low gain direction. A model of a high purity distillation column is used as an example. We study how different identification methods and test approaches will affect model quality for use in control. Also the influence of model structures, namely, MIMO, MISO and SISO parametrizations will be studied. Finally a simple open loop test approach will be proposed. The general conclusions are that a good test design has a stronger impact on the model quality for control than the choice of identification method and model structure; and a SISO structure is not suitable for the problem
Keywords
MIMO systems; chemical technology; distillation; identification; parameter estimation; process control; transfer functions; MIMO; MISO; SISO; closed-loop behaviour; distillation column; identification; ill-conditioned processes; model based control; transfer functions; Automatic control; Computer science; Distillation equipment; Frequency; MIMO; Matrix decomposition; Open loop systems; Process control; Testing; Transfer functions;
fLanguage
English
Publisher
ieee
Conference_Titel
American Control Conference, 2001. Proceedings of the 2001
Conference_Location
Arlington, VA
ISSN
0743-1619
Print_ISBN
0-7803-6495-3
Type
conf
DOI
10.1109/ACC.2001.945885
Filename
945885
Link To Document