DocumentCode :
3425214
Title :
Fault direction method in compensated network using the zero sequence active energy signal
Author :
Loos, Matthieu ; Werben, Stefan ; Kereit, Matthias ; Maun, Jean-Claude
Author_Institution :
BEAMS Energy Dept., Univ. Libre de Bruxelles, Brussels, Belgium
fYear :
2013
fDate :
1-4 July 2013
Firstpage :
717
Lastpage :
723
Abstract :
In medium voltage distribution network, a coil might be placed in the transformer neutral to compensate the zero sequence capacitance of the network. This creates a zero sequence system with very high impedance fault. In case of single phase earth fault, the consequence is a very small faulty current which allows continuous operation even in faulty condition. Several protection devices exist to indicate the fault direction using the transient signal. A new method has been developed by computation of the zero sequence active energy signal to increase the sensitivity of the device regarding the fault impedance. The energy comes from the charging of the zero sequence capacitance of the sound feeder and the imperfection of the Petersen coil. This paper describes the phenomenon behind the algorithm of direction determination and followed by the explanation of the algorithm with simulation tests and recordings from a German DSO.
Keywords :
coils; compensation; earthing; power distribution faults; power distribution protection; power transformers; German DSO; Petersen coil; compensation network; distribution system operator; fault direction method; fault impedance direction; medium voltage distribution network; protection device; single phase earth fault; sound feeder; transformer neutral; zero sequence active energy signal; zero sequence capacitance network; Capacitance; Circuit faults; Coils; Earth; Impedance; Steady-state; Transient analysis; compensated network; fault detection; fault direction; power distribution; power system measurements;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
EUROCON, 2013 IEEE
Conference_Location :
Zagreb
Print_ISBN :
978-1-4673-2230-0
Type :
conf
DOI :
10.1109/EUROCON.2013.6625062
Filename :
6625062
Link To Document :