Application of Laplace transform to analyse delayed current zeros in power stations which employ three-winding step-up transformers
Author
Palazzo, Mirko ; Delfanti, Maurizio
Author_Institution
ABB Switzerland Ltd., Zurich, Switzerland
fYear
2013
fDate
1-4 July 2013
Firstpage
1536
Lastpage
1541
Abstract
The present paper investigates the conditions which make possible the occurrence of delayed current zeros in power stations equipped with three-winding step-up transformers. The current resulting from a fault at the LV-terminals of the three-winding step-up transformer is usually characterized by a high degree of asymmetry and can lead to delayed zeros. Despite the delayed current zeros resulting from this type of fault are not considered in IEEE Standard C37.013-1997 (R2008) and in its amendment IEEE Standard C37.013a-2007, they should be taken into account when studying the suitability of a generator circuit-breaker for the application. The conditions which make possible the occurrence of such a phenomenon are analysed by means of Laplace transform. The corresponding results in time-domain are validated by comparing the waveform of the current obtained with ATP simulations.
Keywords
Laplace transforms; circuit breakers; fault currents; power generation faults; power generation protection; power stations; power transformers; IEEE Standard C37.013-1997 (R2008); IEEE Standard C37.013a-2007; LV-terminal; Laplace transform; delayed current zero; fault current; generator circuit breaker; power station; three winding step-up transformer; Circuit faults; Fault currents; Generators; Laplace equations; Power generation; Power transformers; Transient analysis; Delayed current zeros; Laplace transform; fault currents; generator circuit-breaker; three-winding step-up transformer;
fLanguage
English
Publisher
ieee
Conference_Titel
EUROCON, 2013 IEEE
Conference_Location
Zagreb
Print_ISBN
978-1-4673-2230-0
Type
conf
DOI
10.1109/EUROCON.2013.6625182
Filename
6625182
Link To Document