DocumentCode
3444604
Title
Uncertainties in the Measurement of Power Harmonics and Flicker
Author
Budovsky, Ilya ; Hammond, Greg
Author_Institution
National Meas. Lab., CSIRO, Lindfield, NSW
fYear
2004
fDate
38139
Firstpage
88
Lastpage
89
Abstract
Uncertainties of a precision measurement system developed at NML for traceable calibration of three-phase instruments measuring harmonics of current up to 20 A, voltage fluctuation and flicker are discussed. The analysis shows that current and voltage harmonics up to the 99th and fluctuating voltages can be generated and measured with relative uncertainties close to 1times10-5
Keywords
calibration; electric current measurement; flicker noise; harmonic analysis; measurement systems; measurement uncertainty; power system measurement; voltage measurement; 20 A; current harmonics; measurement uncertainty; power harmonics measurement; voltage fluctuation; voltage harmonics; Amplitude modulation; Current measurement; Delta modulation; Electrical resistance measurement; Harmonic analysis; Measurement uncertainty; Power measurement; Power system harmonics; Testing; Voltage fluctuations;
fLanguage
English
Publisher
ieee
Conference_Titel
Precision Electromagnetic Measurements Digest, 2004 Conference on
Conference_Location
London
Print_ISBN
0-7803-8494-6
Electronic_ISBN
0-7803-8494-6
Type
conf
DOI
10.1109/CPEM.2004.305454