DocumentCode
3444730
Title
A controller in d-q synchronous reference frame for hybrid HVDC transmission system
Author
Torres-Olguin, Raymundo E. ; Molinas, Marta ; Undeland, Tore M.
Author_Institution
Dept. of Electr. Power Eng., Norwegian Univ. of Sci. & Technol., Trondheim, Norway
fYear
2010
fDate
21-24 June 2010
Firstpage
376
Lastpage
383
Abstract
In this paper, a model-based controller is proposed for Hybrid HVDC transmission systems. Hybrid HVDC comprises a Line-commutated Converter (LCC) and a Voltage Source Converter (VSC) which are connected on the same DC link. The VSC regulates the active and reactive power using a model-based controller in a synchronous reference frame while the LCC maintains the DC voltage using a proportional and integral controller. PSCAD/EMTDC simulations illustrates the performance of the Hybrid operation in comparison with CIGRE benchmark HVDC model during normal operation and severe disturbance such as DC fault and AC faults.
Keywords
HVDC power transmission; PI control; power convertors; power transmission control; AC faults; CIGRE benchmark HVDC model; DC fault; PSCAD-EMTDC simulations; d-q synchronous reference frame; hybrid HVDC transmission system; line-commutated converter; model-based controller; proportional and integral controller; voltage source converter; Control systems; Converters; HVDC transmission; PSCAD; Pi control; Power conversion; Power system modeling; Proportional control; Reactive power control; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics Conference (IPEC), 2010 International
Conference_Location
Sapporo
Print_ISBN
978-1-4244-5394-8
Type
conf
DOI
10.1109/IPEC.2010.5542227
Filename
5542227
Link To Document