Abstract :
The performance of a new transformer diagnosis method is tested experimentally. The method is called model-based diagnosis because the diagnosis is based on an identified model of the component, i.e., the transfer function. A single test series is carried out in order to evaluate the sensitivity of the method in transformer diagnosis. The basic purpose of this sensitivity test series is to determine how close the identified transformer model is connected to the physical condition of the modeled transformer. Based on the results of the sensitivity test series it is concluded that the detection of failures and aging phenomena in transformers by transfer functions is dependent on detectable changes in relatively few characteristic transformer parameters, i.e., basically lumped winding capacitances, total losses and core reluctance
Keywords :
power transformers; ageing; core reluctance; failure detection; identified transfer functions; lumped winding capacitances,; sensitivity test; total losses; transformer diagnosis; Aging; Frequency; Power engineering and energy; Power system faults; Power system modeling; Power system reliability; Reliability engineering; Testing; Transfer functions; Voltage transformers;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Electronics Insulation Conference and Electrical Manufacturing & Coil Winding Conference, 1993. Proceedings., Chicago '93 EEIC/ICWA Exposition
Conference_Location :
Chicago, IL
ISSN :
1071-6270
Print_ISBN :
0-7803-0847-6
Type :
conf
DOI :
10.1109/EEIC.1993.631251
Filename :
631251
Link To Document :
بازگشت