Abstract :
Partial discharges (corona) are a symptom of most types of deterioration of high voltage motor and generator stator windings. A new type of partial discharge test is described. It can be performed by plant personnel during normal operation of the machine. The key requirement of the new test is to remove all the interference caused by other sparking and discharging sources in a plant. The test uses either high voltage capacitive sensors or 1000 MHz electromagnetic couplers to detect the discharge signals. The signals are processed by a specialized electronic instrument to remove noise. this test is specially designed for high speed machines
Keywords :
electric generators; 1000 MHz; deterioration; discharge signals; discharging; electromagnetic couplers; electronic instrument; generators; high speed machines; high voltage capacitive sensors; insulation breakdown; interference suppression; motors; partial discharge testing; personnel; sparking; stator windings; Capacitive sensors; Corona; Couplers; Electromagnetic coupling; Interference; Partial discharges; Personnel; Stator windings; Testing; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Electronics Insulation Conference and Electrical Manufacturing & Coil Winding Conference, 1993. Proceedings., Chicago '93 EEIC/ICWA Exposition
Conference_Location :
Chicago, IL
ISSN :
1071-6270
Print_ISBN :
0-7803-0847-6
Type :
conf
DOI :
10.1109/EEIC.1993.631307
Filename :
631307
Link To Document :
بازگشت