DocumentCode
3451553
Title
Analysis of high neutral current in three-phase four-wire multi-grounded distribution feeders
Author
Chang, G.W. ; Chiu, M.J. ; Lee, K.S. ; Hsu, Y.E.
Author_Institution
Dept. of Electr. Eng., Nat. Chung Cheng Univ., Ming-Hsiung, Taiwan
Volume
2
fYear
2003
fDate
7-12 Sept. 2003
Firstpage
531
Abstract
This paper presents a study of investigation and analysis of factors contributing to high neutral line current in a three-phase four-wire multi-grounded distribution system. In the study, the electromagnetic transient program, EMPT/ATP, is used to simulate different scenarios that lead to high neutral line current. Studies show that, in addition to typical imbalance caused by load characteristics, dominant factors contributing to high neutral current include asymmetrical connected types of transformers, failures of distribution feeder capacitor banks, and power theft.
Keywords
EMTP; distribution networks; power transformers; distribution feeder capacitor banks failures; electromagnetic transient program; multigrounded distribution feeders; neutral line current; power theft; Maintenance; Power capacitors; Power system measurements; Power system protection; Power system relaying; Power system reliability; Power system transients; Power transformer insulation; Protective relaying; Wire;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference and Exposition, 2003 IEEE PES
Print_ISBN
0-7803-8110-6
Type
conf
DOI
10.1109/TDC.2003.1335330
Filename
1335330
Link To Document