Title :
OLTC and multiple SVRs in distribution system by using database
Author :
Kawano, Shunsuke ; Yoshizawa, Shinya ; Fujimoto, Yu ; Hayashi, Yasuhiro
Author_Institution :
Dept. of Adv. Sci. & Eng., Waseda Univ., Tokyo, Japan
Abstract :
This paper presents a new method for determining the load drop compensator (LDC) parameters of On-load tap changer (OLTC) and step voltage regulators (SVRs) in the distribution system. Introduction of photovoltaic generation systems (PVs) into a distribution system makes determining the appropriate LDC parameters difficult, which may cause voltage deviation because reverse power flow from PVs affects voltage. Especially in the distribution system in which multiple SVRs are installed, determining the appropriate combination of LDC parameters becomes difficult. In the proposed method, the parameters are reset every hour by choosing one LDC parameter from a database including feasible parameters in the past. To create the database, the proposed method hourly enumerates the feasible parameters utilizing data acquired by SCADA. To evaluate the performance of the proposed method, the amount of voltage deviation of the proposed method will be compared with that of a centralized control method.
Keywords :
centralised control; on load tap changers; photovoltaic power systems; power distribution control; voltage regulators; LDC; OLTC; SCADA; centralized control method; distribution system; load drop compensator; multiple SVR; on-load tap changer; photovoltaic generation systems; reverse power flow; step voltage regulators; voltage deviation; Centralized control; Databases; Load modeling; Numerical models; Regulators; Voltage control; Voltage measurement; Smart Grids; decentralized voltage control; photovoltaic system; power distribution system;
Conference_Titel :
Energy (IYCE), 2015 5th International Youth Conference on
Conference_Location :
Pisa
Print_ISBN :
978-1-4673-7171-1
DOI :
10.1109/IYCE.2015.7180777