Abstract :
At approximately 5:48 a.m. on August 13, 1991, phase B of the main stepup transformers of Niagara Mohawk´s Nine Mile Point Unit 2 (NMP2) Nuclear Power Plant experienced a failure resulting in degraded voltage in phase B of the electrical AC distribution system. The duration of the degraded voltage lasted 12 cycles, the time required to clear the fault and to fast transfer the house loads to alternate offsite sources. The protective relaying schemes accomplished this without any abnormalities. Due to the nature of the fault and its protection, the turbine tripped, resulting in an automatic reactor scram. However, during the first transfer under degraded voltage conditions, five nonsafety-related uninterruptible power supplies (UPSs) tripped. The tripping of these UPSs resulted in the loss of plant process computers, control room annunciation, and a significant portion of nonsafety-related instrumentation and control circuits. The events of that day and the effects of the tripping are described and analyzed here.<>
Keywords :
failure analysis; fission reactor safety; nuclear power stations; power system protection; power transformers; uninterruptible power supplies; Nine Mile Point Unit 2; automatic reactor scram; control circuits; control room annunciation; degraded voltage; electrical AC distribution system; fault; nonsafety-related instrumentation; nonsafety-related uninterruptible power supplies; nuclear power station; plant process computers; protection; protective relaying schemes; stepup transformers; tripping; turbine trip; Automatic control; Circuit faults; Degradation; Power generation; Power system protection; Protective relaying; Transformers; Turbines; Uninterruptible power systems; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Nuclear Science Symposium and Medical Imaging Conference, 1991., Conference Record of the 1991 IEEE
Conference_Location :
Santa Fe, NM, USA
Print_ISBN :
0-7803-0513-2
Type :
conf
DOI :
10.1109/NSSMIC.1991.259156
Filename :
259156
Link To Document :
بازگشت