Abstract
A modified technique for calibrating both the capacitance ratio and dissipation factor (DF) dials of a current-comparator-based high voltage capacitance bridge (CCB-HVCB) has been developed at KRISS. The capacitance ratio and DF dials are calibrated, respectively, in the ratio range from 1/1 to 100/1 and in DF range from 10 × 10-6 to 1 × 10-1. From the calculated and measured values of the corresponding dial balanced readings, the errors in the capacitance ratio an DF dial readings can be derived. This modified calibration technique has been implemented on a commercial version of a NRC developed CCB-HVCB. The comparison results of the calibration performed at KRISS and NRC will be presented and discussed.
Keywords
bridge circuits; calibration; current comparators; KRISS; NRC; capacitance ratio calibration; current comparator; dissipation factor calibration; high voltage capacitance bridge calibration; modified calibration technique; Bridge circuits; Calibration; Capacitance measurement; Capacitors; Councils; Electromagnetic measurements; Measurement standards; Standards development; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Precision Electromagnetic Measurements (CPEM), 2010 Conference on
Conference_Location
Daejeon
Print_ISBN
978-1-4244-6795-2
Type
conf
DOI
10.1109/CPEM.2010.5543413
Filename
5543413
Link To Document