An analysis of temperature of oil-immersed transformer under non-linear load
Author
Thammarat, C. ; Suechoey, B. ; Tadsuan, S. ; Kinnares, V. ; Bunjongjit, S.
Author_Institution
Dept. of Electr. Eng., South East Asia Univ., Bangkok, Thailand
Volume
1
fYear
2004
fDate
21-24 Nov. 2004
Firstpage
517
Abstract
While loading transformer with the non-linear load, the overheating problem occurs and the insulator winding life is reduced. This research presents the oil-immersed transformer temperature test at conductor at high and low voltage side, and temperature test at top oil of oil-immersed transformer. To generate the harmonic current and harmonic voltage, we load the transformer with non-linear load, such as rectifier, heater and capacitor, and record current and voltage data. The results of the testing are calculated and compared with the 2-different methods, the K-factor method and the model method. Finally, the model method temperature is nearly the same as the experimental temperature, so this research is more useful to protect the transformer from overheat.
Keywords
insulators; power transformer insulation; transformer oil; transformer protection; transformer windings; K-factor method; harmonic current; harmonic voltage; insulator winding life; model method; nonlinear load; oil-immersed transformer; overheating problem; temperature analysis; Capacitors; Conductors; Low voltage; Oil insulation; Petroleum; Power transformer insulation; Protection; Rectifiers; Temperature; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology, 2004. PowerCon 2004. 2004 International Conference on
Print_ISBN
0-7803-8610-8
Type
conf
DOI
10.1109/ICPST.2004.1460049
Filename
1460049
Link To Document