Title :
Conduction through surface films on aluminum wire
Author :
Aronstein, Jesse ; Hare, Thomas K.
Abstract :
Conduction through undisturbed surface films on commercial aluminum wire is experimentally evaluated by establishing an area of contact on the wire surface without applying mechanical pressure, using a conductive silver epoxy. The measurements indicate the film conduction is substantially higher than has been estimated on the basis of the properties of pure aluminum oxide. Using applied electrical conditions similar to those of building wire applications, the potential drop is measured to be the same magnitude as is observed in failing aluminum wire connections. The results show that the behavior of failing aluminum connections can be accounted for by the conduction and breakdown properties of the surface film, in the absence of mechanically induced metallic asperity junctions.<>
Keywords :
aluminium; aluminium compounds; building wiring; electrical contacts; reliability; wires (electric); area of contact; building wire; commercial Al wire; conductive Ag filled epoxy; failing Al connections; film conduction; impure Al/sub 2/O/sub 3/ film; potential drop; undisturbed surface films; wire connections; Aluminum; Cable insulation; Conducting materials; Conductive films; Conductors; Impurities; Metal-insulator structures; Surface cracks; Surface resistance; Wire;
Conference_Titel :
Electrical Contacts, 1988., Proceedings of the Thirty Fourth Meeting of the IEEE Holm Conference on
Conference_Location :
San Francisco, CA, USA
DOI :
10.1109/HOLM.1988.16113