DocumentCode
3468146
Title
Efficient parametric identification method for high voltage pulse transformers
Author
Candolfi, Sylvain ; Aguglia, Davide ; Viarouge, Philippe ; Cros, Jerome
Author_Institution
Electr. & Comput. Eng. Dept., Laval Univ., Quebec City, QC, Canada
fYear
2013
fDate
16-21 June 2013
Firstpage
1
Lastpage
6
Abstract
This paper presents a new identification method for a pulse transformer equivalent circuit. It is based on a analytical approximation of the frequency-domain impedance data derived from a no-load test with open-circuited secondary winding and only requires measurements of primary current and voltage without phase data. Compared with time consuming and complex methods based on off-line non-linear identification procedures, this simple method also gives an estimation of the error on the identified parameters. The method is validated on an existing pulse transformer.
Keywords
frequency-domain analysis; pulse transformers; transformer windings; analytical approximation; frequency-domain impedance data; high voltage pulse transformers; off-line nonlinear identification procedures; open-circuited secondary winding; parametric identification method; pulse transformer equivalent circuit; Capacitance; Equivalent circuits; Frequency measurement; Impedance; Inductance; Pulse transformers; Resonant frequency;
fLanguage
English
Publisher
ieee
Conference_Titel
Pulsed Power Conference (PPC), 2013 19th IEEE
Conference_Location
San Francisco, CA
ISSN
2158-4915
Type
conf
DOI
10.1109/PPC.2013.6627549
Filename
6627549
Link To Document