DocumentCode :
3470845
Title :
Robustness of distance relay with Mho characteristic against fault resistance
Author :
Jamali, S. ; Shateri, H.
Author_Institution :
Dept. of Electr. Eng., Iran Univ. of Sci. & Technol., Tehran, Iran
Volume :
2
fYear :
2004
fDate :
21-24 Nov. 2004
Firstpage :
1833
Abstract :
This paper discusses the maximum earth fault resistance, which can be tolerated by a distance relay with Mho characteristic. This is defined as the boundary fault resistance the relay can discriminate between in-zone and out-of-zone faults. The robustness criterion is defined on the basis of the boundary fault resistance. In order to achieve this, the related equations are first derived and then the boundary fault resistance curve is presented. The simulation results for a typical transmission system shows the effectiveness of the proposed robustness criterion for distance relays settings.
Keywords :
electric resistance; power system relaying; power system stability; power transmission faults; power transmission protection; relay protection; robust control; Mho characteristic; arcing faults; boundary fault resistance; distance protection; distance relay; earth fault resistance; in-zone faults; out-of-zone faults; robustness; transmission system; Circuit faults; Earth; Electrical resistance measurement; Impedance; Power system faults; Power system protection; Power system relaying; Protective relaying; Relays; Robustness;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power System Technology, 2004. PowerCon 2004. 2004 International Conference on
Print_ISBN :
0-7803-8610-8
Type :
conf
DOI :
10.1109/ICPST.2004.1460300
Filename :
1460300
Link To Document :
بازگشت