DocumentCode :
3471472
Title :
Transient voltage distribution and interturn voltages in a generator during the commutation of a thyristor bridge load
Author :
Kunakorn, A. ; Hiley, J. ; Smith, K.S.
Author_Institution :
Heriot-Watt Univ., Edinburgh, UK
fYear :
1999
fDate :
1999
Firstpage :
203
Lastpage :
207
Abstract :
This paper presents the distribution along a synchronous generator winding of the leading edge of a notch in the voltage waveform of a synchronous generator supplying a thyristor bridge. The leading edge of the notch is steep enough to cause a nonlinear distribution along the generator winding during the transient period. This nonlinear distribution results in higher interturn voltage than that in a normal operation. The presence of a cable connected between the bridge and the generator as well as the variation of the firing delay angle of the bridge causes a modification of the transient notch depth and then affects the distribution of the notch leading edge along the winding
Keywords :
synchronous generators; connecting cable; firing delay angle; higher interturn voltage; interturn voltages; nonlinear distribution; normal operation; synchronous generator winding; thyristor bridge; thyristor bridge load commutation; transient notch depth modification; transient period; transient voltage distribution; voltage waveform;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Electrical Machines and Drives, 1999. Ninth International Conference on (Conf. Publ. No. 468)
Conference_Location :
Canterbury
ISSN :
0537-9989
Print_ISBN :
0-85296-720-9
Type :
conf
DOI :
10.1049/cp:19991019
Filename :
816385
Link To Document :