• DocumentCode
    3473470
  • Title

    Transient response characteristics of new HVDC transmission system based on new converter transformer

  • Author

    Li, Yong ; Luo, Longfu ; Nakamura, Kazuo ; Rehtanz, C. ; Zhang, Jie ; Xu, Jiazhu ; Liu, Fusheng

  • Author_Institution
    Coll. of Electr. & Inf. Eng., Hunan Univ., Changsha
  • fYear
    2008
  • fDate
    6-9 April 2008
  • Firstpage
    1873
  • Lastpage
    1877
  • Abstract
    The new HVDC transmission system adopts the new converter transformer and the corresponding inductive filtering method, and its electrical topology structure is completely different from that of the existential HVDC transmission system. For the change of the controlled system, the transient response characteristics of the new HVDC transmission system will be accordingly changed when it adopts the standard control model that the traditional HVDC transmission system adopts. Referring to the parameters of the main circuit of the OGRE HVDC first benchmark model, this paper designs a similar benchmark model of the new HVDC transmission system based on the technical characteristics of the new converter transformer and the corresponding inductive filtering method, which mainly contains the rated parameters of the new converter transformer and the inductive filtering device. Then, the typical transient response characteristics of the new HVDC transmission system have been analyzed and simulated by PSCAD/EMTDC. The results express that the new HVDC transmission system, which adopts the standard control model that the HVDC transmission engineering adopts, has a good transient response characteristic, and can operate stably when subjecting to various typical disturbance.
  • Keywords
    HVDC power convertors; HVDC power transmission; power transformers; HVDC transmission system; converter transformer; electrical topology structure; inductive filtering device; inductive filtering method; transient response characteristics; Control systems; Filtering; HVDC transmission; PSCAD; Power harmonic filters; Reactive power; Transient response; Virtual colonoscopy; Voltage control; Wiring; Inductive filtering method; new HVDC transmission system; new converter transformer; transient response characteristic;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Utility Deregulation and Restructuring and Power Technologies, 2008. DRPT 2008. Third International Conference on
  • Conference_Location
    Nanjuing
  • Print_ISBN
    978-7-900714-13-8
  • Electronic_ISBN
    978-7-900714-13-8
  • Type

    conf

  • DOI
    10.1109/DRPT.2008.4523712
  • Filename