Protection of distributed generation (DG) interconnection
Author
Tholomier, D. ; Yip, T. ; Lloyd, G.
Author_Institution
Areva T&D, La Prairie, QC, Canada
fYear
2009
fDate
10-13 March 2009
Firstpage
1
Lastpage
15
Abstract
Selection of the DG interconnection protective relay is based on several criteria such as power system characteristics, the dynamic response of the generator, the system grounding, the DG transformer connection, etc., as well as the protection policy of the utility and coordination requirements. The interconnection protection IED design can be summarized as follows: disconnection of DG plants when no longer operating in parallel with the utility grid; protection of the utility grid from damage caused by connection of the DG plants (voltage transients, fault current supplied by DG, reclosing without check sync, etc.); protection of the DG plant from damage caused by the utility grid; coordination with other protective relays should be made to prevent unnecessary trips; possible implications on utility protections must be analysed when a DG is connected, depending on the characteristics of the network, such as the loss of coordination or sensitivity, reclosing coordination, etc.
Keywords
distributed power generation; dynamic response; earthing; power grids; power system interconnection; power transformers; relay protection; DG transformer connection; distributed generation interconnection; dynamic response; fault current; power system; protection policy; protective relay; reclosing coordination; system grounding; utility grid; voltage transients; Character generation; Distributed control; Grounding; Power generation; Power system dynamics; Power system interconnection; Power system protection; Power system relaying; Protective relaying; Voltage; Distributed Generation; IEEE P-1547; Interconnection Protective Relay; Renewable Energy Sources;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Systems Conference, 2009. PSC '09.
Conference_Location
Clemson, SC
Print_ISBN
978-1-4244-5248-4
Type
conf
DOI
10.1109/PSAMP.2009.5262332
Filename
5262332
Link To Document