Title :
10 kV insulated compact distribution line supported by composite spacers in urban area
Author :
Zeng, Rong ; He, Jinliang ; Chen, Shuiming ; Fu, Fangwei ; Guan, Zhicheng
Author_Institution :
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
Abstract :
Adopting insulated conductors and compact configuration has become the tendency in the renovation of distribution network in China. Advantages of compact configuration are discussed. Superiority of compact configuration against lightning protection has been analyzed. The reason that breakage faults occurred on compact distribution tine with polymeric spacer is discussed. It is due to the bad pollution flashover performance of the polymeric spacer cast with polycarbonate. Polycarbonate Is not suitable for outdoor Insulation. A new triangle composite spacer, which Is suitable for heavy pollution areas, Is designed to prevent breakage faults caused by leakage current. 28 cm is chosen as phase spacing. The application effects of the developed composite spacers are very good.
Keywords :
insulator contamination; lightning protection; polymer insulators; power distribution faults; power distribution lines; power distribution protection; 10 kV; 28 cm; China; breakage faults; compact configuration; composite spacers; insulated compact distribution line; insulated conductors; leakage current; lightning protection; outdoor insulation; pollution flashover performance; polymeric spacer; urban area; Conductors; Dielectrics and electrical insulation; Flashover; Frequency; Lightning; Pollution; Polymers; Safety; Trees - insulation; Urban areas;
Conference_Titel :
Industrial and Commercial Power Systems, 2003. 2003 IEEE Technical Conference
Print_ISBN :
0-7803-7771-0
DOI :
10.1109/ICPS.2003.1201490