DocumentCode :
3481817
Title :
Corrected winding eddy-current harmonic loss factor for transformers subject to nonsinusoidal load currents
Author :
Elmoudi, A. ; Lehtonen, M. ; Nordman, H.
Author_Institution :
Helsinki Univ. of Technol., Helsinki
fYear :
2005
fDate :
27-30 June 2005
Firstpage :
1
Lastpage :
6
Abstract :
The assumption that the transformer windings eddy loss rise in proportion to the square of the harmonic order is reasonable for small conductors and low harmonics with errors on the conservative side only for a combination of large conductors and higher harmonics. This paper presents a corrected harmonic loss factor by taking into account the depth of penetration, which leads to more accurate estimation of the increased transformer winding losses under non-sinusoidal load currents.
Keywords :
eddy current losses; power system harmonics; transformer windings; eddy-current harmonic loss factor; nonsinusoidal load currents; transformer windings; transformers; Clamps; Conductors; Eddy currents; Frequency; Impedance; Phase locked loops; Power system harmonics; Temperature; Transformer cores; Windings; Harmonic loss factor; IEEE C57-110-98; Transformers;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Tech, 2005 IEEE Russia
Conference_Location :
St. Petersburg
Print_ISBN :
978-5-93208-034-4
Electronic_ISBN :
978-5-93208-034-4
Type :
conf
DOI :
10.1109/PTC.2005.4524421
Filename :
4524421
Link To Document :