• DocumentCode
    3482759
  • Title

    Influences of european three minute-silence on operation of UCTE power system

  • Author

    Kuzle, I. ; Mandic, N. ; Tesnjak, S.

  • Author_Institution
    Univ. of Zagreb, Zagreb
  • fYear
    2005
  • fDate
    27-30 June 2005
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    In September 11th 2001 was attack on New York and in March 11th 2004 was attack on Madrid. As an expression of solidarity with the American and Spain people, Europe has declared 14 September and 15 March a days of mourning, respectively. During the three minute-silence period experimental tests were carried in Croatian National Dispatching Centre. Results indicated that the load, in the first case decreased about 2030 MW with frequency increased 113 mHz. In the second case frequency increased 83 mHz and load decreased about 1500 MW. The evaluation of the performed measurements showed control behavior of the European power system.
  • Keywords
    power system control; power system measurement; American; Croatian National Dispatching Centre; Europe; Madrid; New York; UCTE power system; frequency 113 mHz; frequency 83 mHz; power 1500 MW; power 2030 MW; Control systems; Dispatching; Europe; Frequency measurement; Performance evaluation; Power measurement; Power system measurements; Power systems; Terrorism; Testing; frequency; frequency measurement; power frequency characteristic; power system; primary control;