DocumentCode
3483132
Title
Punctured insulator examination of a string insulator
Author
Pattanadech, N. ; Yutthagowit, P.
Author_Institution
King Mongkut´´s Inst. of Technol. Ladkrabang, Bangkok
fYear
2005
fDate
27-30 June 2005
Firstpage
1
Lastpage
5
Abstract
This paper represents a punctured insulator detection method of a string insulator using a corona camera which can detect the ultraviolet light (partly corona phenomena) obtained from the high electric field stress of air around the tested insulators. It was found that the corona camera could detect the corona phenomena of the energized proper insulators at the inception and the higher voltage. In case of the energized improper insulators, the corona phenomena could be detected also at the inception voltage but it could not if the voltage of the improper insulator reached its punctured voltage. Using this normal principle, the punctured insulators connected with the good insulators of the string insulators can be detected.
Keywords
corona; insulator testing; corona camera; electric field stress; punctured insulator detection; string insulator testing; ultraviolet light detection; Cameras; Corona; Dielectrics and electrical insulation; Helium; IEC standards; Insulator testing; Power engineering and energy; Solids; Stress; Voltage; corona; punctured insulator; string insulator;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Tech, 2005 IEEE Russia
Conference_Location
St. Petersburg
Print_ISBN
978-5-93208-034-4
Electronic_ISBN
978-5-93208-034-4
Type
conf
DOI
10.1109/PTC.2005.4524493
Filename
4524493