DC frame fault & ground fault field testing on TriMet Portland light rail system
Author :
Pham, Kinh D. ; Heilig, Thomas ; Looijenga, Kai ; Ramirez, Xavier
Author_Institution :
Elcon Associates, Inc, Portland, OR, USA
fYear :
2005
fDate :
16-18 March 2005
Firstpage :
151
Lastpage :
164
Abstract :
Until recently, TriMet traction power substations (TPSs) utilized a low resistance grounding system for the dc switchgear and rectifier equipment enclosures. The TPS negative bus was connected to a dc ground mat through a grounding diode. In addition to the basic dc overcurrent and rate-of-rise relays, each substation is provided with a low resistance frame fault current relay (device 64 C) and a negative-to-ground potential relay (device 64 V). Recently, TriMet has conducted several field tests: a) bolted frame fault tests, by applying 750 Vdc to the dc switchgear enclosure with the grounding diode connected and then with the grounding diode removed, b) ground fault tests, by connecting the OCS contact wire to an OCS pole ground rod (the ground fault tests were done with and without the diode), c) ground fault tests simulating an arcing ground fault, with a 9 ohm resistor inserted in series between the OCS contact wire and the OCS pole ground rod. This paper provides the test data and discusses the results of these frame fault and ground fault field tests. Technical analysis including personnel safety considerations are performed for various test configurations. The analysis will be focused on ground fault detection since most ground faults are undetected because of the very low ground fault current magnitudes, which are normally not detected by the rate-of-rise relay.
Keywords :
earthing; fault currents; fault diagnosis; light rail systems; rectifiers; relays; substations; switchgear; switchgear testing; traction power supplies; 64 V; 750 V; 9 ohm; DC frame fault; OCS pole ground rod; TriMet Portland light rail system; TriMet traction power substation; arcing ground fault; bolted frame fault test; dc ground mat; dc overcurrent; dc switchgear enclosure; frame fault current relay; ground fault field testing; grounding diode; negative-to-ground potential relay; rate-of-rise relay; rectifier equipment; Diodes; Fault currents; Fault detection; Frame relay; Grounding; Light rail systems; Substations; Switchgear; System testing; Wire;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Rail Conference, 2005. Proceedings of the 2005 ASME/IEEE Joint
Print_ISBN :
0-7918-3752-1
Type :
conf
DOI :
10.1109/RRCON.2005.186071
Filename :
1460835
Link To Document :
بازگشت