• DocumentCode
    3483840
  • Title

    Application of percentage cross differential relay in EHV double lines

  • Author

    Wang, Q.P. ; Dong, X.Z. ; Bo, Z.Q. ; Caunce, B.R.J. ; Apostolov, A.

  • Author_Institution
    Tsinghua Univ., Beijing
  • fYear
    2005
  • fDate
    27-30 June 2005
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    The cross differential protection used to protect parallel double transmission lines is able to offer fast operation without the need for communication link. However, the conventional cross differential relay is not sensitive enough to protect EHV transmission lines because of the requirement for high setting values. In this paper, a percentage cross differential element is used to improve the performance of the conventional cross differential relay. A Voltage start and a phase selection element are also used to improve the stability of the percentage cross differential relay. The percentage cross differential relay is implemented in to latest numeric platform. Extensive tests using EMTP and RTDS show that the relay is able to give significantly improve the performance of the conventional cross differential relay by extending the coverage of the instant tripping zone and increasing the reliability of the protection scheme.
  • Keywords
    power system protection; power system reliability; power system stability; EHV double lines; EMTP; RTDS; percentage cross differential relay; phase selection element; power stability; reliability; voltage start; Circuit faults; Digital relays; Distributed parameter circuits; EMTP; Power system protection; Power system reliability; Power transmission lines; Protective relaying; Stability; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Tech, 2005 IEEE Russia
  • Conference_Location
    St. Petersburg
  • Print_ISBN
    978-5-93208-034-4
  • Electronic_ISBN
    978-5-93208-034-4
  • Type

    conf

  • DOI
    10.1109/PTC.2005.4524531
  • Filename
    4524531