  • Abstract
    The objective of the impulse tests on distribution transformers is to evaluate the winding insulation performance against lightning. Therefore, the acquired wave shapes must not present failure evidences. The key point on these cases is that some measurement equipments rarely show failure signals, mainly signals due to high frequency oscillation, considering as perfect a failed transformer. This paper discusses some mathematical model and testing results that shows that some high frequency oscillations are related to turn-to-turn failures.
  • Keywords
    power transformer testing; distribution transformer impulse test; high frequency oscillation; winding insulation performance; Automatic testing; Capacitance measurement; Circuit testing; Frequency; Impulse testing; Inductance; Laboratories; Oscilloscopes; Power transformer insulation; Shape; Circuit Modeling; Testing; Transformers; Transient Analysis;