Abstract :
The paper analyzes the performance of a ROCOF relay and looks at the factors that affect its detection capability, such as load type and the impact of load power factors. It also considers how ROCOF can maloperate during system transients. The later section of this paper describes a new LOM detection technique based on a GPS synchronized phasor measurement system that compares the angular difference between the utility network voltage phasors and the distributed generator voltage phasors. The performance of the proposed technique is shown to be more reliable than ROCOF.
Keywords :
distributed power generation; phase measurement; power factor; power system measurement; relay protection; transient analysis; GPS synchronized phasor measurement system; angular difference; distributed generation islanding detection; distributed generator voltage phasors; load power factors; network voltage phasors; rate of change of frequency relay; system transients; Distributed control; Distributed power generation; Frequency; Power generation; Power system protection; Power system relaying; Reactive power; Relays; Signal generators; Voltage;