DocumentCode
3486944
Title
A topology error identification method directly based on collinearity tests
Author
Lourenço, Elizete M. ; Costa, Antonio J A Simões ; Clements, Keven A. ; Cernev, Rafael A.
Author_Institution
Fed. Univ. of Parana, Curitiba
fYear
2005
fDate
27-30 June 2005
Firstpage
1
Lastpage
6
Abstract
A method for topology error identification based on collinearity tests involving Lagrange multipliers and the columns of the corresponding covariance matrix is presented. It relies on a geometric interpretation of multipliers associated with the equality constraints which model circuit breaker status in generalized state estimation. The method is conceptually simple and its implementation requires little computational effort, being therefore suitable for real-time applications. Results of several simulated cases conducted at the substation level on the IEEE 30-bus network are used to illustrate the performance of the proposed technique.
Keywords
circuit breakers; covariance matrices; power system state estimation; IEEE 30-bus network; Lagrange multipliers; circuit breaker; collinearity tests; covariance matrix; equality constraints; generalized state estimation; power system real time operation; substation; topology error identification method; Circuit breakers; Circuit simulation; Circuit testing; Circuit topology; Computational modeling; Covariance matrix; Lagrangian functions; Solid modeling; State estimation; Substations; Bad Data Analysis; Power System Real-time Operation; Power System State Estimation;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Tech, 2005 IEEE Russia
Conference_Location
St. Petersburg
Print_ISBN
978-5-93208-034-4
Electronic_ISBN
978-5-93208-034-4
Type
conf
DOI
10.1109/PTC.2005.4524695
Filename
4524695
Link To Document