Title :
Uncertainty estimate of a split-core Rogowski coil for high AC current
Author :
Suomalainen, E.P. ; Hällström, J.
Author_Institution :
Centre for Metrol. & Accreditation (MIKES), MIKES, Espoo, Finland
Abstract :
The use of Rogowski coil for metrology purposes is investigated. This paper discusses processes influencing the measurement uncertainty, proposes solutions to reduce their effect, and gives estimates on the magnitude of the resulting uncertainties. The aim of this work is to study the applicability of a split-core Rogowski coil for power frequency calibration on currents from 10 A to 10 kA.
Keywords :
calibration; coils; compensation; measurement uncertainty; current 10 A to 10 kA; high AC current; magnitude estimation; measurement uncertainty; power frequency calibration; split-core Rogowski coil; temperature compensation; uncertainty estimation; Coils; Uncertainty;
Conference_Titel :
Precision Electromagnetic Measurements (CPEM), 2010 Conference on
Conference_Location :
Daejeon
Print_ISBN :
978-1-4244-6795-2
DOI :
10.1109/CPEM.2010.5544844