Abstract :
Lightning strokes with a large amount of energy sometimes occur on the Sea of Japan coast in winter. Winter lightning often damages overhead power distribution lines, in particular, those supplying power to high structures located in mountainous areas. The authors have investigated that the ratio of surge arrester outages with respect to all damaged installations on such power distribution lines is largest at approximately 50%. They have examined the effectiveness of installing two pairs of surge arresters in parallel on a single pole as a method for preventing distribution surge arrester outages experimentally. They have clarified that to install surge arresters in parallel is effective in reducing the energy absorbed by surge arresters if these surge arresters have the almost same discharge voltage and voltage-current characteristics
Keywords :
power distribution lines; Lightning strokes; Sea of Japan; absorbed energy reduction; discharge voltage; distribution surge arresters; overhead power distribution; parallel installation effectiveness; power system lightning protection; surge arrester outages; voltage-current characteristics;
fLanguage :
English
Publisher :
iet
Conference_Titel :
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
Conference_Location :
London
ISSN :
0537-9989
Print_ISBN :
0-85296-719-5
Type :
conf
DOI :
10.1049/cp:19990640
Filename :
817302
Link To Document :
بازگشت