• DocumentCode
    3488117
  • Title

    Transient impedance of grounding rods

  • Author

    Gonos, I.F. ; Topalis, F.V. ; Stathopulos, I.A.

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Nat. Tech. Univ. of Athens, Greece
  • Volume
    2
  • fYear
    1999
  • fDate
    1999
  • Firstpage
    272
  • Abstract
    The aim of this paper is the correlation of the transient impedance and its parameters with the stationary resistance of simple grounding systems. Impulse current tests of the standard form 8/20 μs were performed on several types of equilateral triangles and single driven rods of different lengths. The injected current in the grounding system and the developed potential were recorded, resulting in the determination of the time variation of the transient impedance. Further mathematical analysis of the experimental results led to simple linear relations between the parameter of transient impedance and the stationary resistance. The results provide useful information for the design of a grounding system and the measures for the protection of installations from lightning strokes
  • Keywords
    power system protection; developed potential; equilateral triangles; grounding rods; grounding system design; injected current; installation protection; linear relations; mathematical analysis; power system lightning protection; single driven rods; stationary resistance; transient impedance;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
  • Conference_Location
    London
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-719-5
  • Type

    conf

  • DOI
    10.1049/cp:19990646
  • Filename
    817308