Abstract :
The condition of service aged paper-oil insulations can be assessed by measuring the dielectric response of the insulation. The paper deals with the interpretation of experimental results of return voltage measurements and discusses the relevance of different measurement conditions and the meaningfulness of the different diagnostic parameters chosen. Special emphasis is taken on the p-factor, a parameter that seems to be appropriate for all types of insulating materials.
Keywords :
insulating oils; paper; voltage measurement; dielectric response; insulations diagnosis; paper-oil insulations; return voltage measurements; Cable insulation; Current measurement; Dielectric materials; Dielectric measurements; Dielectrics and electrical insulation; Electrodes; Equivalent circuits; Polarization; Power transformer insulation; Voltage measurement; Boundary Polarization; Dielectric Time Constants; Maxwell-Model; Return Voltage Method;