• DocumentCode
    3488388
  • Title

    Reduction of switching transients in the operation of induction motor drives

  • Author

    Rao, M. Venu Gopala ; Naveed, Syed A. ; Amaranath, J. ; Kamakshaiah, S. ; Singh, B.P.

  • Author_Institution
    Jawaharlal Nehru Technol. Univ., Hyderabad, India
  • fYear
    2005
  • fDate
    11-14 Sept. 2005
  • Firstpage
    388
  • Lastpage
    391
  • Abstract
    The aim of the paper is the study of the over voltages due to switching and current chopping by vacuum circuit breaker in high voltage motor system. Hence these studies will provide means of introducing a suitable protective device surge arrester. The influences of the vacuum circuit breaker´s high voltage interrupting capability, cable length, has been traced out to produce a sort of general view of the over voltage phenomena in actual network with surge arrestors. It is seen that high voltage interrupting capability is important for high power motors connected by cables to the vacuum circuit breakers. In the present work transients are reduced up to 21% by using surge arrester.
  • Keywords
    arresters; induction motor drives; overvoltage protection; switching transients; vacuum circuit breakers; cable length; current chopping; high power motors; high voltage interrupting capability; high voltage motor system; induction motor drives; over voltage phenomena; protective device surge arrester; switching transients; vacuum circuit breaker; Arresters; Breakdown voltage; Circuit breakers; Circuit simulation; Ignition; Induction motor drives; Surge protection; Switchgear; Switching circuits; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrets, 2005. ISE-12. 2005 12th International Symposium on
  • Print_ISBN
    0-7803-9116-0
  • Type

    conf

  • DOI
    10.1109/ISE.2005.1612405
  • Filename
    1612405