Title
Major arc flash + good practices = no injuries
Author
Rachford, Joe
Author_Institution
Gallatin Steel, Ghent, KY, USA
fYear
2010
fDate
1-5 Feb. 2010
Firstpage
53
Lastpage
55
Abstract
This case study will describe a major 43 cal/cm2 arc flash fault at a 3,000 amp, 34.5 kV, Motor Operated Air Break (MOAB) Switch that destroyed the switch and the nearby 3,000 amp, 34.5 kV breaker. There were no injuries due to the procedures to operate the devices remotely from a nearby control house.
Keywords
arcs (electric); electrical safety; substations; MOAB; MOAB switch; arc flash fault; injuries; motor operated air break; substation arrangement; Arc discharges; Blades; Injuries; Maintenance engineering; Steel; Switches; Arc Flash Fault; Case Study; No Injuries;