Abstract :
The present paper is devoted to evaluation of transformers ageing. In this work 100 set transformers have been selected in order to take samples from transformer´s oil. By direct measuring of deterioration of paper insulation (degree of de-polymerization) and deterioration by-products in oil, insulating papers condition have been studied. Transformer ageing has simulated with an appropriate model based on dissolved gas and furan content in order to evaluation of aging.
Keywords :
chemical analysis; power transformers; remaining life assessment; chemical analysis methods; degree of depolymerization; dissolved gas; furan content; life assessment; paper insulation; transformers ageing; Aging; Chemical analysis; Degradation; Dielectrics and electrical insulation; Moisture; Oil insulation; Petroleum; Power transformer insulation; Power transformers; Thermal stresses; de-polymerization and furan derivate; transformer´s oil; transformers age reminding;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Electronics Electrical Drives Automation and Motion (SPEEDAM), 2010 International Symposium on
Conference_Location :
Pisa
Print_ISBN :
978-1-4244-4986-6
Electronic_ISBN :
978-1-4244-7919-1
Type :
conf
DOI :
10.1109/SPEEDAM.2010.5545108
Filename :
5545108
Link To Document :
بازگشت