Abstract
Diagnostic tests were performed on a 275 kV prefabricated cable joint insulator using a new test technology, the X-ray induced partial discharge (XIPD) test system developed at Ontario Hydro Technologies. Special shields were designed to facilitate the evaluation of PD characteristics of the large epoxy casting. The test chamber was PD free to 600 kV; discharges from controlled voids inserted near the conductor were readily detected. A PD sensitivity of 0.08 pC was achieved during testing at up to 600 kV. The cable joint insulator remained PD free under X-ray irradiation to the target test voltage of 420 kV
Keywords
power cable insulation; 275 kV; 420 kV; 600 kV; PD sensitivity; X-ray induced partial discharge testing; X-ray irradiation; XIPD testing; controlled voids; diagnostic tests; epoxy casting; insulation breakdown tests; power cable joint insulator; test chamber;