Title :
Combined broad and narrow band multichannel PD measurement system with high sensitivity for GIS
Author :
Neuhold, S.M. ; Schmatz, M.L. ; Hässig, M. ; Spühler, M.M. ; Storf, G.
Author_Institution :
FKH Zurich, Switzerland
Abstract :
A computer controlled GIS (gas insulated switchgear) PD (partial discharge) measurement system is presented which combines UHF broad and narrow band PD measurements with high sensitivity, multichannel performance and near real-time response. Each measurement channel consists of a low noise broadband sensor amplifier with automated high voltage transient protection, a full band power/envelope detector, a narrow band spectrum analyzer interface and a computerized display unit. With 0.1 to 2.0 GHz frequency range, 3 dB noise figure, 40 dB of sensor amplifier gain, full flashover and switching transient protection, twelve measurement channels, less than 0.1 second response time and a user friendly computer interface, the presented system is optimally suited for on-site commissioning tests, for laboratory testing during development and for long term monitoring of complex GIS. This system allows the detection, localization, identification and monitoring of fault sources using a fully electrical method
Keywords :
gas insulated switchgear; 0.1 s; 0.1 to 2 GHz; UHF broad band PD measurements; UHF narrow band PD measurements; flashover protection; gas insulated switchgear; measurement channel; multichannel PD measurement system; sensor amplifier gain; switching transient protection;
Conference_Titel :
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
Conference_Location :
London
Print_ISBN :
0-85296-719-5
DOI :
10.1049/cp:19990908