• DocumentCode
    3497871
  • Title

    Acoustic emissions caused by the corona discharge in an oil-tank

  • Author

    Sakoda, T. ; Arita, Takaya ; Nieda, H. ; Otsubo, M. ; Honda, C. ; Ando, Kiyoini

  • Author_Institution
    Dept. of Electr. Eng., Kumamoto Inst. of Technol., Japan
  • Volume
    5
  • fYear
    1999
  • fDate
    1999
  • Firstpage
    164
  • Abstract
    Measurements of sonic and ultrasonic waves caused by corona discharges were performed based on an acoustic emission (AE) technique, to diagnose the deterioration of insulation and its location in an oil filled pole transformer. The detected signals in these measurements were analyzed by means of a fast Fourier transform (FFT) and their properties were discussed. It was found that the AE signals due to the Lamb waves caused in a thin steel tank can be easily recognized by the FFT analyses of initial stages of the detected AE signals. This indicates that the accuracy on location of the AE sources in the transformer can be improved. Also, it was shown that a low pass filter was effective to improve the accuracy of location
  • Keywords
    power transformer insulation; Lamb waves; acoustic emissions; corona discharge; fast Fourier transform; insulation deterioration; low pass filter; oil filled pole transformer; oil-tank; signals analysis; sonic waves measurement; thin steel tank; ultrasonic waves measurement;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
  • Conference_Location
    London
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-719-5
  • Type

    conf

  • DOI
    10.1049/cp:19990911
  • Filename
    818263