DocumentCode :
3498083
Title :
Characterisation of partial discharges in oil impregnated pressboard insulation systems
Author :
Nerkar, Y.P. ; Narayanachar, M.N. ; Nema, R.S.
Author_Institution :
Dept. of High Voltage Eng., Indian Inst. of Sci., Bangalore, India
Volume :
5
fYear :
1999
fDate :
1999
Firstpage :
208
Abstract :
Partial discharge (PD) measurement and interpretation is one of the most useful diagnostic tools for quality assurance testing during the design, manufacture and life assessment of electrical equipment. Pressboard-oil insulation continues to be a major component in the insulation design of EHV transformers. As tests on practical systems are not always feasible due to cost and time factors, model systems tests are gaining importance. In the present work a model insulation system consisting of oil impregnated pressboard with uniform field electrode arrangement has been tested for its behaviour under PDs. It is shown that by defining a modified scale parameter for the Weibull distribution it is possible to take into account the effect of both smaller and larger magnitude PD pulses. The modified scale parameter serves as a good index for characterising PD behaviour in the oil impregnated pressboard insulation system studied
Keywords :
impregnated insulation; EHV transformers; PD pulses; Weibull distribution; diagnostic tools; electrical equipment; insulation design; life assessment; oil impregnated pressboard insulation systems; partial discharge interpretation; partial discharge measurement; partial discharges characterisation; quality assurance testing; uniform field electrode arrangement;
fLanguage :
English
Publisher :
iet
Conference_Titel :
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
Conference_Location :
London
ISSN :
0537-9989
Print_ISBN :
0-85296-719-5
Type :
conf
DOI :
10.1049/cp:19990922
Filename :
818274
Link To Document :
بازگشت