DocumentCode
3498102
Title
Analysis and suppression of continuous periodic interference for on-line PD monitoring of power transformers
Author
Wang, Cliangchang ; Jin, Xianhe ; Cheng, T.C. ; Shibo Zhang ; Wang, Zongdong ; Dong, Xnzhu ; Zhu, Delicng
Author_Institution
Dept. of Electr. Eng., Univ. of Southern California, Los Angeles, CA, USA
Volume
5
fYear
1999
fDate
1999
Firstpage
212
Abstract
The key to on-line partial discharge (PD) monitoring of power transformers is how to suppress interference effectively. This paper reports an interference qualitative and quantitative analysis on site using a fast Fourier transform (FFT) technique. Various periodic interferences have been found, which emanated from the carrier communication, thyristor switching, and high frequency protection signals of power system as well as radio broadcasting signals. LMS adaptive digital filter and FFT threshold digital filter can be used to eliminate continuous periodic noises for on-line PD monitoring. However, they suffer from their own intrinsic weaknesses. Therefore, a multi-band-pass digital filter based on FFT has been developed. It is a much better method for the purpose of suppressing continuous periodic interference
Keywords
power transformer testing; FFT; FFT threshold digital filter; LMS adaptive digital filter; carrier communication; continuous periodic interference suppression; fast Fourier transform; high frequency protection signals; multi-band-pass digital filter; on-line PD monitoring; partial discharge monitoring; power system; power transformers; radio broadcasting signals; thyristor switching;
fLanguage
English
Publisher
iet
Conference_Titel
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
Conference_Location
London
ISSN
0537-9989
Print_ISBN
0-85296-719-5
Type
conf
DOI
10.1049/cp:19990923
Filename
818275
Link To Document