DocumentCode
3498269
Title
On-site application of an advanced PD defect identification system for GIS
Author
Lapp, A. ; Kranz, H.-G. ; Hücker, T. ; Schichler, U.
Author_Institution
Bergische Univ., Wuppertal, Germany
Volume
5
fYear
1999
fDate
1999
Firstpage
252
Abstract
This paper examines the identification reliability of automated partial discharge (PD) diagnosis systems for common PD defects in gas insulated switchgear (GIS) under practical industrial conditions. The influence of the reference database on diagnosis results as well as new PD evaluation tools like Δu/Δφ-pattern based on phase resolved pulse sequence analysis (PRPSA) are investigated. Especially, the abilities of the PRPSA are examined to identify PD defects with about 70-200 useful PD pulses per second near inception voltage (50 Hz AC stress)
Keywords
partial discharge measurement; Δu/Δφ-pattern; 50 Hz; GIS; PD evaluation tools; advanced PD defect identification system; automated partial discharge diagnosis systems; gas insulated switchgear; identification reliability; inception voltage; phase resolved pulse sequence analysis;
fLanguage
English
Publisher
iet
Conference_Titel
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
Conference_Location
London
ISSN
0537-9989
Print_ISBN
0-85296-719-5
Type
conf
DOI
10.1049/cp:19990933
Filename
818285