• DocumentCode
    3498269
  • Title

    On-site application of an advanced PD defect identification system for GIS

  • Author

    Lapp, A. ; Kranz, H.-G. ; Hücker, T. ; Schichler, U.

  • Author_Institution
    Bergische Univ., Wuppertal, Germany
  • Volume
    5
  • fYear
    1999
  • fDate
    1999
  • Firstpage
    252
  • Abstract
    This paper examines the identification reliability of automated partial discharge (PD) diagnosis systems for common PD defects in gas insulated switchgear (GIS) under practical industrial conditions. The influence of the reference database on diagnosis results as well as new PD evaluation tools like Δu/Δφ-pattern based on phase resolved pulse sequence analysis (PRPSA) are investigated. Especially, the abilities of the PRPSA are examined to identify PD defects with about 70-200 useful PD pulses per second near inception voltage (50 Hz AC stress)
  • Keywords
    partial discharge measurement; Δu/Δφ-pattern; 50 Hz; GIS; PD evaluation tools; advanced PD defect identification system; automated partial discharge diagnosis systems; gas insulated switchgear; identification reliability; inception voltage; phase resolved pulse sequence analysis;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
  • Conference_Location
    London
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-719-5
  • Type

    conf

  • DOI
    10.1049/cp:19990933
  • Filename