DocumentCode :
3498473
Title :
Effect of mechanical pressure and silicone grease on partial discharge characteristics for model XLPE transmission cable joint
Author :
Nadolny, Z. ; Braun, J.M. ; Densley, R.J.
Author_Institution :
Ontario Hydro Technol., Toronto, Ont., Canada
Volume :
5
fYear :
1999
fDate :
1999
Firstpage :
297
Abstract :
This paper reports on the effects of mechanical pressure and silicone grease on the partial discharge (PD) characteristics at EPR-epoxy interfaces in model cable joints. An ultra wide band PD detection system was used. The PD parameters investigated are: rise time, width, fall time, amplitude, inception voltage and frequency of pulses. PD can cause degradation and eventually lead to breakdown. The presence of air bubbles or contaminants at interfaces enhances the local electric field and initiate PD. The effectiveness of mechanical pressure and/or silicone grease to reduce PD activity was demonstrated
Keywords :
XLPE insulation; EPR-epoxy interfaces; XLPE transmission cable joint; air bubbles; amplitude; breakdown; contaminants; inception voltage; local electric field; mechanical pressure; partial discharge characteristics; pulse fall time; pulse frequency; pulse rise time; pulse width; silicone grease; ultra wide band PD detection system;
fLanguage :
English
Publisher :
iet
Conference_Titel :
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
Conference_Location :
London
ISSN :
0537-9989
Print_ISBN :
0-85296-719-5
Type :
conf
DOI :
10.1049/cp:19990944
Filename :
818296