Sensitive on-site PD measurement and location using directional coupler sensors in 110 kV prefabricated joints
Author
Craatz, P. ; Plath, R. ; Heinrich, R. ; Kalkner, W.
Author_Institution
CableTechnique, Berlin, Germany
Volume
5
fYear
1999
fDate
1999
Firstpage
317
Abstract
To verify the reliability of 110 kV XLPE cable joints a long term prequalification test was carried out at IPH. 12 joints of various manufacturers were integrated in a circular 110 kV XLPE cable test loop. The short distances between the joints required selective PD measurement and localisation location to measure PD from each joint separately. Therefore directional coupler sensors (DCS) were integrated at each joint to provide a sensitive and unequivocal PD measurement and localisation
Keywords
power cable insulation; 110 kV; PD localisation location; XLPE cable joints; XLPE cable test loop; directional coupler sensors; on-site PD location; on-site PD measurement; prefabricated joints; prequalification test; reliability; selective PD measurement;