• DocumentCode
    350140
  • Title

    Laboratory-relevant corona inception of a 1-m-airgap under impulse voltage

  • Author

    Rühling, F. ; Heilbronner, F. ; Díaz, R.R. ; Ortéga, P.

  • Author_Institution
    Inst. of High Voltage Eng. & Electr. Power Transmission, Tech. Univ. Munchen, Germany
  • Volume
    3
  • fYear
    1999
  • fDate
    1999
  • Firstpage
    39
  • Abstract
    The corona inception voltage of a point-plane airgap is studied in a climatic chamber under various test conditions: polarity of the (1-cosine) impulse voltage, humidity, artificially generated positive and negative ions, agitated air in the laboratory and various electrode materials. The lowest inception voltages are obtained, when the electrode is not treated, the laboratory´s air is not agitated, negative polarity is applied, humidity is high and negative ions are generated artificially. Under these conditions, the measured inception voltages reach minimum values and their statistical spread is reduced significantly
  • Keywords
    air gaps; 1 m; agitated air; artificially generated negative ions; artificially generated positive ions; corona inception voltage; electrode materials; humidity; impulse voltage; lowest inception voltages; point-plane airgap; test conditions;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
  • Conference_Location
    London
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-719-5
  • Type

    conf

  • DOI
    10.1049/cp:19990694
  • Filename
    816707